Gauge, Transmitter or LCD Transmitter? A Dwyer Differential Pressure Shortlist
Most differential pressure questions on air and non-combustible gas come down to one decision: does somebody need to look at a dial, does a controller need a 4-20 mA signal, or does the fitter on the roof need both? Dwyer covers all three cases inside the same accessories ecosystem, which is why the three devices below get compared so often. They share the same 1/8 in barbed or NPT connections and the same physical envelope, but they are not interchangeable once you look at accuracy, power and price.
Ranges are the first filter. The Magnehelic 2000 covers an enormous spread, from 0-60 Pa up to 0-200 kPa, in 81 published ranges, with compound versions around zero for filter monitoring on either side of atmospheric. The transmitter families start at much lower spans, 0-0.25 in w.c. or 60 Pa, and stop at 0-200 in w.c., which covers cleanroom, duct static and filter loading work but not high-pressure gas lines.
Where the three models part company
| Model | Output | Range coverage | Accuracy | Supply | Best fit |
|---|---|---|---|---|---|
| Series 2000 Magnehelic | 4 in (101.6 mm) analog dial, no electrical output | 81 ranges, 0-60 Pa to 0-200 kPa, compound ranges available | ±2 % of full scale; ±3 % on the 0-100 Pa, 0-125 Pa and 10 mm ranges, ±4 % on the 0-60 Pa and 6 mm ranges | None | Local indication of filter loading, fan static, cleanroom positive pressure |
| Series 616 | 4-20 mA, two-wire | 0-1 to 0-200 in w.c.; differential psid versions to 0-100 psid | ±0.25 % of full scale (616C version ±1.0 %) | 10-35 VDC | Feeding a BMS or PLC input where range and budget are tight |
| Series 616WL | 4-20 mA plus three-digit LCD | From 0-0.25 in w.c. (60 Pa) upward | ±0.50 % of full scale, display ±0.5 % | 12-30 VDC, two-wire, 900 Ω max loop | Outdoor or dusty installations needing a local readout and a signal |
Two of the differences are easy to miss on a quotation sheet. The 2000 gauge has a pressure limit of 15 psig for standard versions, with 35 psig and 80 psig options, and a relief plug that opens near 25 psig on the standard unit; a transmitter with a 5 psig maximum on its low ranges will not survive the same abuse. The 616 and 616WL are rated 0 to 140 °F (-17.8 to 60 °C), while the dial gauge is published for -6.7 to 60 °C. On a rooftop air handling unit in winter, that gap decides the choice.
- Choose a range so the normal operating point sits between 40 % and 70 % of full scale. A gauge running at 5 % of its span wastes most of its accuracy.
- Below 0-125 Pa, accept the wider ±3 % or ±4 % tolerance or step up to a transmitter with a tighter published figure.
- Mount the Magnehelic dial vertically. The transmitter can hang in any orientation, which matters when the tapping points are on top of a duct.
- Check the loop: 616WL allows up to 900 Ω at 24 V, the 616 up to 1250 Ω, so long cable runs and a 250 Ω input resistor are usually fine without a separate supply.
If the answer is "we need to see it and log it", buy the 616WL and skip the extra gauge. If the answer is "the operator walks past it twice a shift", the 2000 dial is still the cheapest reliable way to show a clogged filter, and the 4-20 mA version can be added later on a second tapping point without reworking the panel.