Ordering a MADAS Gas Regulator? Five Questions to Settle First

Author: EFFSEN AUTOMATION | HONGKONG | Date: 2026-11-27

MADAS builds gas pressure regulators, filters and safety devices in Verona, Italy, and their equipment shows up on burner trains, kilns and boiler rooms all over the world. The catalogue is bigger than most people expect, so here are the five questions that come up most often before an order is placed – with straight answers.

Q: What does a MADAS regulator actually do on a gas train?

It holds the downstream pressure constant at the value you set, even while the upstream pressure and the burner's flow demand wander around. That is not optional: Italian standard UNI-CIG 8042 requires a pressure regulator on the inlet line of every burner, and EN 88 class devices are the usual way to comply across Europe. If the outlet pressure drifts, the burner's excess air drifts with it, and efficiency and emissions go wrong together.

Q: Which inlet pressure class do I need?

MADAS splits its regulator range by maximum inlet pressure: versions for P1 up to 0.5 bar, 0.5 to 1 bar, and 1 to 2 bar. The classic RG/2MC sits in the low class – inlet from 20 mbar up to 1 bar – and delivers outlet pressures from 8 to 500 mbar at flows from roughly 15 up to 3,000 Nm³/h of natural gas, with governing accuracy around ±5% and lock-up pressure below 1.2 times the set point. Pick the class from the actual upstream pressure at your meter, not from the nominal network rating.

Q: Do I still need a separate slam-shut valve, or can the regulator do the safety job?

Several MADAS regulator series are available with OPSO (over-pressure shut-off), UPSO (under-pressure shut-off), or both plus a RELIEF function built into the same body. That means the monitor and working regulator plus the safety lock can live in one footprint instead of three separate devices. Whether the local gas code accepts an integrated solution instead of a standalone safety shut-off valve is worth confirming with your inspector early – it changes the train layout and the bill of materials noticeably.

Q: How do I size it?

Size from the pressure-loss versus flow curve, not from the port size. Take the example used in the sizing notes: inlet 30 mbar, outlet set at 25 mbar, so the regulator is allowed to eat 5 mbar of pressure drop. Find 5 mbar on the curve chart, cross it with your flow – say 75 Nm³/h – and the curve you land on right of that point is the size that will actually hold the set pressure at full load. Sizing too large is a real failure mode: an oversized regulator hunts and wears the seat.

Q: What about connections, temperatures and special environments?

The range runs from DN 15 up to DN 150. Threaded connections follow EN 10226 on the smaller sizes, flanges up to DN 100 per ISO 7005, with PN16 bodies and elastomers (nitrile diaphragms on the common models) good for roughly −15 to +60 °C of ambient and media temperature. For hazardous areas there are ATEX versions for Zones 1, 21, 2 and 22, and for burner tuning there are zero governors and gas/air ratio regulators in the same catalogue family. Quick reference for the most-ordered series:

RG/2MC quick factsValue
Inlet pressure P120 mbar to 1 bar
Outlet pressure P28 to 500 mbar
Flow range (natural gas)15 to 3,000 Nm³/h
Governing accuracy / lock-up±5% / ≤ 1.2 × P2
StandardsEN 88 (class A), UNI-CIG 7430/8042
ConnectionsDN 15–50 threaded (EN 10226); DN 65–100 flanged (ISO 7005)
Body / temperaturePN16 die-cast aluminum, brass, steel; −15 to +60 °C

If your job involves filtered-and-regulated inlet air for the burner, the FRG/2MC pairs the regulator with an integral filter element in one casting – one less flange joint and one less leak path on the train.