Bender iso685 Paperwork, Sorted: Datasheet, Manual, Brochure and Catalogue

Author: EFFSEN | HONGKONG | Date: 2026-11-19

Bender keeps its technical documentation on bender.de as plain PDFs behind no login, which makes the insulation monitoring range unusually easy to research before you buy. The awkward part is knowing which of the four files you actually need. A commissioning engineer wants the manual. A panel designer wants the datasheet. A maintenance planner usually wants the brochure, because it explains the measuring principle in language he can pass on to a shift supervisor. This page points at each one directly, all on Bender's own server, and all four were opened and checked before publishing.

The device behind most of this paperwork is the ISOMETER iso685. It monitors insulation resistance on unearthed IT systems, AC up to 690 V and DC up to 1000 V, and it covers the applications that make conventional residual current monitoring useless: rectifier-fed drives, UPS and battery banks, phase-controlled heaters, switch-mode power supplies and systems with high leakage capacitance. Everything below applies to the -P variants, the ones with the integrated locating current injector.

Start with the datasheet when you are sizing

The iso685-…-P datasheet (PDF) is the four-page document to open first. It lists the four ordering variants and their article numbers: iso685-D-P at B91067030 with the display built in, iso685W-D-P at B91067030W for the extended -40 to +70 °C range, and the two separate-display versions iso685-S-P at B91067230 and iso685W-S-P, which need an FP200 front panel to be operated at all. Nominal system voltage is AC 0 to 690 V at 1 to 460 Hz or DC 0 to 1000 V, and supply voltage is a wide 24 to 240 V AC or DC, so the same device runs off a 24 V control bus or a 230 V panel supply.

Two numbers on that sheet decide most projects. The response values for alarm 1 and alarm 2 are adjustable from 1 kΩ to 10 MΩ in two independent ranges, and the permissible system leakage capacitance goes up to 1000 µF depending on the measuring profile selected. On a large drive system with long shielded cable runs, that second figure is the one that rules devices out. The datasheet also gives the response time as typically 4 s with a test resistance of half the alarm value at 1 µF, the ±10 V or ±50 V measuring voltage, and the 110 × 108 × 93 mm case dimensions.

The manual is where the wiring lives

Terminal assignments, the commissioning wizard sequence, the meaning of each predefined profile, the Modbus register map and the ISOnet settings for coupling several IT systems together are all in the iso685-…-P operating manual (PDF). This is also the file that explains the EDS side of the system. With the locating current injector built in, the iso685-D-P can drive EDS44x insulation fault locators and up to twelve measuring current transformers, with EDS440 resolving 2 to 10 mA of locating current and EDS441 going down to 0.2 to 1 mA. The device sets the EDS parameters over the Bender bus and shows the located feeder by the name you gave that channel, which is why commissioning is normally done from the front panel or the web server rather than from a laptop tool.

Two documents for the people who sign off

The iso685 brochure (PDF) is short and mostly pictures, but it contains the clearest explanation of the AMPPlus measuring method and of why insulation monitoring belongs on an IT system in the first place. Hand it to anyone who asks why the plant is not simply earthed and fitted with RCDs. The fourth file, Bender's insulation monitoring product overview (PDF), is the one to keep for range questions: it puts the iso685 alongside the smaller iso175 and isoHR685 devices, the EDS locator families and the coupling and measuring accessories, so you can see whether the application really needs the flagship unit or a compact one will do.

One practical note before ordering. The -S variants have no display and no keys, so they cannot be configured on their own; budget for an FP200 panel or plan to set them up over the network. And when a system already has Bender monitors installed, check the firmware and the ISOnet device count in the manual before adding another unit to the same coupled network.