Installing an Alfa Electric Cabinet Heater or Air Conditioner? Start With the Right Paperwork
Alfa Electric publishes a genuinely useful paper trail for its enclosure climate control range: one full product catalog plus a separate, freshly dated catalog for each product family, and behind those, per-model installation manuals. Everything is hosted on alfaelectric.com as plain PDF files, so there is no login, no form, and no registration wall. If you are quoting a cabinet cooling retrofit or wiring an anti-condensation heater into a control panel, the documents below are the ones worth saving locally.
The range divides neatly into five families. Air conditioners (AVC wall-mount, AVE outdoor wall-mount, ARC roof-mount, ARK 19-inch rack) all use rotary compressors and a digital thermostat that handles compressor on/off setpoints, start delays, anti-short-cycling and a maximum-temperature alarm. Heating is covered by DIN-rail PTC heaters (STHT/HT/MHT) and fan-assisted FSHT units from 250 to 750 W. ALFATORR roof fans handle forced ventilation, and the ETUH electronic hygro-thermostat controls both temperature and humidity on a 35 mm DIN rail.
| Family / Series | What it does | Key figures from the manuals |
|---|---|---|
| AVC / AVE / ARC / ARK air conditioners | Cooling for indoor, outdoor and rack cabinets | Rotary compressor, R134a, digital thermostat with alarm functions, IP54 when mounted on an equal-rated cabinet |
| STHT / HT / MHT PTC heaters | Anti-condensation heating on 35 mm DIN rail | ".001" versions carry a fixed set-point thermostat (heats below 5 °C, stops above 15 °C); inrush can hit 6× rated current, so use a delayed fuse |
| FSHT fan-assisted heaters | Higher-output anti-condensation heating | 250 / 400 / 500 / 750 W, 230 V or 115 V variants, green status LED, keep 300 mm clearance at the air outlet and 100 mm at the inlet |
| ALFATORR roof fans | Forced ventilation, air flows inside-out | IP44 as standard; the F-suffix version is IP54 with a washable filter under the roof grille |
| ETUH hygro-thermostat | Controls heaters on humidity or temperature | 0 / +60 °C ±1 K with 2 K hysteresis, 20–90 %RH with 5 % hysteresis, UL file E348803 |
Family catalogs (official PDF, 2024–2025 editions)
Full catalog 2024 — the complete range in one document, useful as a desk reference: ALFAELECTRIC Catalogue EN 2024 (PDF)
Air conditioning — AVC, AVE, ARC and ARK series with cooling capacities and dimensional data: air-conditioner.pdf (PDF)
Heating — STHT, HT, MHT and FSHT heaters with wattage and terminal layouts: heating.pdf (PDF)
Ventilation — ALFATORR roof fans and side filter fans: ventilation.pdf (PDF)
Control — mechanical thermostats, hygrostats and the ETUH electronic controller: control.pdf (PDF)
Lighting — cabinet LED bars and lamps with motion-sensor options: lighting.pdf (PDF)
Installation and user manuals
AVC200 indoor wall-mount air conditioner — wiring, start-up, spare parts and the EU declaration of conformity for the AVC/AVE/ARC series: UMA-CDZ-AVC200xxAE-04.pdf (PDF)
STHT / HT / MHT PTC heaters — DIN-rail clipping, the fixed 5 °C set-point logic, and the delayed-fuse warning: UMA-ACH-STHT-HT-MHT-rev00.pdf (PDF)
FSHT fan-assisted heaters — model table from FSHT250 to FSHT751 and the 300/100/60 mm clearance rules: FSHT-istruzioni-rev01.pdf (PDF)
ETUH electronic hygro-thermostat — independent temperature and humidity setpoints with hysteresis values: ETUH-instruction.pdf (PDF)
ALFATORR roof fans — electrical connection, the IP44 vs IP54(F) distinction and filter cleaning steps: ALFATORR-istruzioni-230V.pdf (PDF)
One practical note before you order: the manuals repeatedly stress that heaters and thermostats must be installed inside the enclosure, vertically, with cables below, and only by qualified personnel with the power disconnected. If your cabinet sits in a wet or dusty corner, pair an FSHT or STHT heater with the ETUH rather than a plain thermostat — the independent humidity trigger is what stops condensation forming on cold panels between cycles.