ABB A260-30-11-80 Contactor
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V.Operated with control voltage, versions from 24….690 AC, 50 and 60 Hz
Dimensions
140 mm
180.5 mm
227 mm
5.4 kg
Technical
3
0
1
1
3P
Main Circuit 690 V
Main Circuit 50 / 60 Hz
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 400 A
(690 V) 40 °C 400 A
(690 V) 55 °C 350 A
(690 V) 70 °C 290 A
(415 V) 55 °C 260 A
(440 V) 55 °C 240 A
(500 V) 55 °C 240 A
(690 V) 55 °C 220 A
(380 / 400 V) 55 °C 260 A
(220 / 230 / 240 V) 55 °C 260
(110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
(110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
(110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
(415 V) 140 kW
(440 V) 140 kW
(500 V) 180 kW
(690 V) 200 kW
(380 / 400 V) 140 kW
(220 / 230 / 240 V) 80 kW
8 x Ie AC-3
10 x Ie AC-3
gG Type Fuses 500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2400 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1100 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2600 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2400 A
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Main Circuit 8 kV
(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
5 million