Sizing a Gefran KS Range: What Half a Percent of Full Scale Really Costs

Author: EFFSEN AUTOMATION | HONGKONG | Date: 2026-11-20

The Gefran KS is a small stainless transmitter built around a thick-film strain gauge deposited directly on a stainless diaphragm, and the whole family spans 1 bar to 1000 bar with either a two-wire 4-20 mA or a three-wire 0-10 V output. It is aimed squarely at fluid power: hydraulic power packs, presses, pumps, injection moulding machines, compressors and mobile hydraulics, where shock, vibration and fast pressure peaks are normal rather than exceptional. The housing is AISI 304, the wetted parts are AISI 430F and 17-4 PH, and the sensor responds in under a millisecond, which is fast enough to see a pressure spike that a slower transmitter would average away.

The most common mistake with this family is choosing the range by the system's relief valve setting rather than by the pressure the machine actually works at. The published statement of accuracy is better than plus or minus 0.5 percent of full scale, and that figure already includes non-linearity, hysteresis, repeatability and both offsets. On a 400 bar unit, half a percent is two bar of uncertainty before anything has drifted. A 60 bar hydraulic circuit fitted with a 400 bar transmitter therefore throws away most of its resolution for the sake of headroom it does not need. The data sheet also notes that the operating range is intended from 0.5 percent to 100 percent of full scale, so a range around one and a half times working pressure is a more useful compromise than one sized for the burst rating.

Peaks are handled by design rather than by range padding. Overpressure is twice the nominal range without degrading performance, and the burst containment is four times nominal; a 100 bar transmitter is expected to survive 200 bar of overpressure and to contain 400 bar before it fails structurally. That is a margin for transients, water hammer and valve slam, not a licence to run the sensor continuously at relief pressure. If a machine genuinely sits near its relief setting for long periods, the next range up is the honest choice, and the accuracy trade-off is smaller than the fatigue risk.

Output selection is usually decided by cable length and by the controller, but on this family it also has a safety consequence. The 4-20 mA version runs on 10 to 30 V and is the natural choice for long runs and for analog PLC inputs, since a current loop does not lose accuracy to cable resistance. The 0-10 V version needs 15 to 30 V and suits short connections to a controller or indicator. Both are described as compact, oil-free and all stainless with SIL2 certification to IEC/EN 62061 as standard, with one exception worth reading twice: the 0-5 V and 0-10 V variants are not SIL2 rated. A safety function that depends on the pressure signal must therefore be built on the current output.

Temperature is the second place where the data sheet rewards a careful read. Process temperature is rated from minus 40 to plus 125 degrees Celsius and ambient from minus 40 to plus 105, but the compensated band is narrower, minus 20 to plus 85. Inside that band the zero and span drift is about 0.015 percent of full scale per degree Celsius, typically, with 0.02 percent as the maximum. Outside it the transmitter still works, but the accuracy claim no longer holds, which matters on a press where the manifold sits close to hot oil and the ambient around the block climbs well past 60 degrees. Long-term stability is quoted under 0.2 percent of full scale per year, and vibration and shock ratings of 20 g and 100 g respectively are high enough that the mounting bracket, not the sensor, is usually the weak point.

Finally, the installation details that get skipped. Ingress protection is IP65 or IP67 depending on the mating connector, so the connector choice decides the rating, not the sensor body. The body should be grounded through the machine, signal cable should be routed away from power cable, and for SIL applications the data sheet asks for a non-distributed power circuit with cable length kept under 30 metres. Process connections include G 1/4 and G 1/2 male to DIN 3852-E among the options, and the sealing method has to match the port: a DIN 3852-E port expects a sealing ring at the base, and wrapping the thread with tape instead is the fastest way to a leaking hydraulic block. Zero and span are fixed at the factory, so there is nothing to adjust in the field, which also means a transmitter that reads low is telling you about the process or the wiring rather than about its calibration.