A False Low-Coolant Alarm on a Generator: Specifying a BEDIA CLS-40
A generator set in a unheated plant room kept dropping offline on a false low-coolant alarm. The original float switch had worked fine for a few seasons, then started chattering as the coolant aged and left a light film on the float. The maintenance team wanted a replacement that would ignore that film, run on the existing 24 V supply, and survive the washdown the room occasionally got. That is a fairly ordinary BEDIA CLS-40 application, and the details of why are worth walking through.
The CLS-40 does not use a float at all. It measures capacitance at around 600 kHz and looks at the dielectric constant of whatever surrounds the probe. Water-based coolant sits at roughly εr 35–85, while oils and fuels sit down at 1.8–6. That gap is the whole trick: the sensor only has to tell two very different dielectrics apart, so a thin film of residue on the stem does not move the reading the way it moves a mechanical float. The change to a capacitive probe alone removed the chatter.
Supply was the next decision. This site runs a 24 V DC system, and the CLS-40 is rated for 9–36 V DC, so it drops in without a separate supply. It is worth being precise about the family here, because BEDIA makes a near-neighbour: the CLS-45 is a 4.5–18 V device aimed at lower-voltage harnesses. Ordering the wrong one is an easy mistake when both are sold as “CLS”. Current draw is under 8 mA either way, which is negligible on a generator's control supply.
The probe was specified with an M14×1.5 thread and an ISO 15170 connector, the combination most often stocked for engine coolant and oil applications. Two installation details mattered more than the part number. First, the probe has to sit at least 7 mm off the tank wall and be fully wetted before it will switch, so the boss location was chosen with the low-level mark in mind rather than where it was easiest to drill. Second, the connector was torqued down properly – 25 N·m on the M14 thread – because IP67 is only guaranteed with the mating connector correctly fitted; done properly the assembly reaches IP69K, which is what the washdown called for.
What the commissioning actually checked
Power-up is not instant: the unit runs a ~2 second self-check, and the standard fault-indication delay is around 7 seconds. On the bench that looks like sluggishness, but in service it is exactly what you want, since it rides out the sloshing that happens when a generator starts and the coolant surges. The technician filled the tank to the low mark, confirmed the output changed after the delay, then deliberately low-level tested with the probe dry. The whole exercise took ten minutes and there has been no false alarm since. Working temperature spans −40 to +125 °C, so the unheated room is no concern; for oil service the same probe is rated to +150 °C. If the tank geometry ever changes, BEDIA offers extension tubes in 350, 450 and 550 mm lengths (order numbers 421660 / 421661 / 421659) and a mounting bracket, 454134, which saves drilling a new boss.