Model: VBMS 230-20
AC-3 Rated Operating Power: 1.5 kW
Rated Operating Voltage (50/60Hz): 3 × 240V ±10% (according to DIN EN 50160 / IEC 38)
Conventional Enclosed Thermal Current Iin = Ie (Motor Contactor): 16 A
Braking Current Range: 2 ... 20 A
Maximum Braking Time: 10 s
Maximum Braking Frequency (Braking Current 10A):
Braking time 5s: Once every 25s
Braking time 10s: Once every 50s
Maximum Braking Frequency (Braking Current 20A):
Braking time 5s: Once every 60s
Braking time 10s: Once every 120s
Switch-off to Braking Delay Time: 500 ms
Braking Voltage: 0 ... 110 V DC
Maximum Conductor Cross-sectional Area (per Terminal): 2.5 mm²
Ambient Temperature: 0°C ... 45°C
Storage Temperature: -25°C ... 75°C
Weight: 0.6 kg